Filtrine Open Loop POC-5000-540 Chiller
With DUAL 25 HP Compressor, 3 HP Pump, 320 gal Storage Capacity
Filtrine‘s POC chillers recirculate a clean coolant at constant temperature and pressure to increase the stability and consistency of water cooled machines and instruments. Choose from two condenser configurations to match your specific site requirements. The POC-5000 is available with either an fan cooled condenser inside the chiller housing (POC-5000-A) or a water cooled condenser (POC-5000-W) for hookup to city or tower water.
POC - Open Loop Chillers - pump liquid from an open tank or sump, through the chiller and back to the sump. An adjustable thermostat senses the return liquid temperature, cycling the chiller to insure constant temperature in the sump.
Specifications:
Features
- Energy saving design where the compressor only runs as needed
- Close temperature control
- Welded stainless steel cooling tank
- Uses “Ozone Safe – Low Global Warming Potential (GWP)” HFO refrigerant
- Optional stainless steel exterior
Options
Condenser Models: AR, Remote Air cooled condenser furnished separately for mounting on roof; W, water cooled condenser for hookup to city or tower water; AR-WP, Remote air cooled condenser; complete unit made weather-resistant for outdoor installation
Design the perfect cooling system for any application. See Options & Accessories.
Details
Cooling Capacity
BTU/HR: 540,000
Watts: 158,264
Rating Conditions:
Coolant Discharge Temperature: 68oF [20oC]
Ambient Temperature: 90oF [32oC]
Tank Capacity (Gal): 320
Compressor Motor (HP): DUAL 25
Circulating Pump (HP): 3
Cabinet Dimensions (in): 116″W x 62″D x 70″H
Shipping Weight (lbs): 5600 (2520 kg)
Downloads
- Filtrine HCAI OSHPD Special Seismic Certification Preapproval (OSP) #OSP-0369
- Filtrine Process Liquid Chiller Guide
- Filtrine Chiller Options & Accessories
- Filtrine Heater and Chiller Options Specification Sheet
- Filtrine Other Coolant Interchanger (OCO) Option Specification Sheet
- Filtrine Chiller Model 664K-R407C Remote Air Cooled Condensers
- Filtrine Process Chiller PCP/POC-5000 Chiller Specifications Sheet
Related Applications
Laboratory Equipment
Ensure accuracy of non-ferrous cooling circuits for electron microscopes, blood cooling, diffusion pumps, spectrometers, scanners, NMR magnets and many other sensitive devices with a Filtrine laboratory equipment chiller. Close temperature control and pure coolant are what Filtrine customers have come to expect with a Filtrine chiller.