Capacity | Outlet Temp | ||
MBH* | Watts | °F | °C |
70.0 | 20510 | 68 | 20 |
48.0 | 14067 | 50 | 10 |
25.0 | 7327 | 30 | -1 |
*1,000 BTUs per hour
Standard Dimensions:
72"W x 35"D x 60"H
The dissipated heat from water cooled lasers is removed by Filtrine chillers which provide water temperatures above the dew point to avoid condensation. Solid state controls provide temperature stability within ±0.5OF and an ambient tracking thermostat is included. An optional pure system ensures that deionized water coolant comes in contact with stainless steel or polypropylene only.